Model PND
  Technical Reference Sheet
  Phase-Guard   Model PND

             UL LISTED 573U
   INDUSTRIAL CONTROL EQUIPMENT

The master relay coil in this model is de-energized when conditions are normal.
Upon phase loss or phase unbalance(12% or more)  the master relay will energize
after the time delay has elapsed (standard 1 ½ seconds).

The master relay will not react to a total power interruption of any duration.

The PND model will automatically reset when fault has been corrected and balanced
Voltage is restored
            Standard features
            Model PND includes led indicators for normal (green) and phase loss (yellow) as a standard
            feature.  It also includes DPDT output relay with 30 amp contact rating.

           A total power loss will not affect the model PND since the master relay is normally
           de-energized.  This characteristic helps eliminate the possibility of nuisance tripping during
           storms and other outages.
           The PND model is recommended for applications involving a main breaker or  bolted pressure
           switch which must be manually reset after an outage occurs.

Available Options